135°F - Explosion Proof Mounting UL (MODEL 302-EPM)
Explosion proof for installation in hazardous locations.
Has hexagonal grip bushing with 1/2’ conduit threads for attach-ment to threaded hub cover of series JL fixture fitting as manu-factured by Killark Electric Co., or equal. Must be hand tightened only. For Interior use.
Special Considerations
Temp. Rating °F. Max Ceiling Temp. °F.
135 115
194 155
Detectors are not directionally effected, can be mounted horizontally or vertically.
Detectors have a smooth ceiling UL rating of 50’ x 50’
(2500 sq. ft.) on 8 to 10 ft. ceilings.
Detectors, hub covers, or outlet boxes must never be installed in direct sunlight.
Refer to NFPA STAN-DARD 72 for spacing and other considerations.
Electrical Rating
Voltage Current
6-125 VAC 5 amps
6-25 VAC 1 amp
125 VDC 0.5 amp